Energy Tech Laboratories EDP70 User Manual

Page 38

Advertising
background image

page

38 --

MI00/10056 rev.1--05/2001

5.4

Signal connections

a) Emergency Power Off

When the connection between terminals 1 and 2 is opened, the UPS will stop, and it will
automatically restart when the switch is closed. This allows a remote E.P.O. to be installed, in series
with the standard one installed inside the UPS. (See Para. 9.1)

Warning: To avoid unauthorized stopping, it is strongly recommended that some form of security switch be used..

b) Battery charge inhibited

By removing the link between terminals 3 and 4, the battery charge will be inhibited, and a warning
message will be displayed.

Possible uses of this could be one, or more, of the following:

connect the above terminals to a contact which will be opened if there is Hydrogen within the
battery compartment(s).

In this way the cause of hydrogen generation will be stopped, and a warning about the operating
status of the system will be displayed.

connect the above terminals to a contact which will be opened when the UPS is supplied by a
Generator (it should be an auxiliary contact of the Line <-> Generator changeover).

In this way it will be possible to limit the power supplied by the Generator to the only value
required to supply the critical loads, and not to charge the battery until the mains supply returns.

In this way it is possible to use a Generator having a power rating less than the maximum input
power of the UPS.

Also in this case a warning about the operating status of the system will be displayed.

c) Thermostick connector (50/80kVA only)

This connection provides the customer with remote control over the output transformer
Overtemperature Alarm (T

CORE

= 180°C).

NOTE:

If more than one of the above applications (or similar) are installed, the contacts MUST be
connected in series.

Advertising