10.7

Battery Test

The EDP70 PLUS has an automatic battery control function which checks the condition of the battery periodically
without affecting the output in any way. While this test is being carried out, the message »TESTING BATTERY»
will appear.
This test can also be activated manually. Return to the main title page so that ‘SYSTEM NORMAL’ is displayed.

UPS xx KVA

SYSTEM NORMAL

system normal message

PRESS SIMULTANEOUSLY

(The test is disabled if the BATTERY TEST selected is NONE)

UPS xx KVA

TESTING BATTERY

The battery test is underway and takes approx. 1 minute.
If the test is completed without giving off any alarm, then
the system returns to normal operating mode; otherwise,
the alarm message »BATTERY FAULT» is displayed.

10.8

Battery Autonomy Test

The EDP70 PLUS has a battery autonomy test which disables the rectifier manually.
To carry out this test, return to the main title page so that ‘SYSTEM NORMAL’ is displayed.

UPS xx KVA

SYSTEM NORMAL

system normal message

PRESS SIMULTANEOUSLY and keep pressed for 2 seconds

(The test is diabled if the BATTERY TEST selected is NONE)

UPS xx KVA

TESTING AUTONOMY

The battery starts to discharge completely thereby
allowing the autonomy to be checked. Once the battery
has been discharged, the test comes to an end
automatically and the rectifier restarts.

To interrupt BATTERY autonomy Test, at any time: PRESS SIMULTANEOUSLY

and

keep

pressed for 2 seconds

10.9

Resetting data loss manually

If the message »NOT CALIBRATED» appears on the main title page, this means that data (language and total
number of mains failures) which do not directly affect the functioning of the machine have been lost. Despite this,