Caution, Warning – Energy Tech Laboratories EDP70 User Manual

Page 27

Advertising
background image

MI00/10056 rev.1--05/2001-- page

27

CAUTION!

WARNING!

All power connection must carried out by qualified

licensed personnel experienced

in wiring this type of equipment

The safety ground wire must

be connected before the power input cables

The correct phase rotation

(phase A leads B leads C)

must be observed on the UPS terminals.

An input grounded neutral conductor is required

(24/36kVA only)

In maintenance by-pass operation,

the UPS components are de-energized,

with the exception of input/output terminals,

battery cabinet, input matching voltage

transformer (for 480/208 configuration) and isolating

transformer (for 50 and 80kVA).

All input power (AC and DC) must be disconnected to ensure

complete isolation