3 insulation monitoring, 1 insulation monitoring device – SMA SC 500CP-10-JP User Manual

Page 25

Advertising
background image

SMA Solar Technology AG

3  Product Description

User Manual

SCCP-JP-BA-A4-en-12

25

3.7.3 Insulation Monitoring

3.7.3.1 Insulation Monitoring Device

Depending on the order option, an insulation monitoring device can monitor the insulation resistance of the PV system in

ungrounded PV arrays.
In the operating state "MPP load operation", the insulation resistance of the entire system, from the PV array to the

MV transformer, will be measured.
If the Sunny Central is in the operating state "Grid monitoring", only the insulation resistance from the PV array to the

Sunny Central will be measured.

Figure 9: Insulation monitoring device in the Sunny Central

A measuring circuit and a relay with a change-over contact are integrated in the insulation monitoring device.
The insulation monitoring device is connected between the PV voltage and the grounding conductor. The contacts of the

relay are routed to the connection area and can be used to trip a signal light or siren. The characteristics of the relay are

indicated in the circuit diagram.
If the insulation resistance falls below the warning threshold specified in the RisoCtlWarn parameter, the measuring

circuit closes and the LED ALARM1 on the insulation monitoring device lights up. The error message 3601‒ Warning

insulation error is generated by the inverter. Simultaneously, the insulation monitoring device activates the relay with

changeover contact. This relay is integrated in the Sunny Central.
If the insulation resistance falls below the error threshold (1 kΩ), an insulation error has occurred and the LEDs ALARM1

and ALARM2 on the insulation monitoring device light up. In this case, the operating behavior of the inverter can be set

via parameters as follows:

• If the parameter IsoErrIgn is set to Off, the measuring circuit issues a disturbance when the insulation resistance falls

below the error threshold, the Sunny Central switches off and issues the error message 3501 - Insulation error.

The LEDs ALARM1 and ALARM2 are lit.

• If the parameter IsoErrIgn is set to On, the error message from the measuring circuit is ignored when the insulation

resistance falls below the error threshold. The Sunny Central continues to feed into the grid and generates the error

message 3504 ‒ Insulation error ignored.

• If the parameter IsoErrIgn is set to Run and the insulation resistance falls below the error threshold, the error

message from the measuring circuit will only be ignored if the inverter is in feed-in operation. In feed-in operation,

the Sunny Central continues to feed in and issues the error message 3504 ‒ Insulation error ignored. If the

insulation resistance falls below the error threshold in another operating state, the error will not be ignored and the

Sunny Central will not go into feed-in operation. The error message 3501 ‒ Insulation error appears on the touch

display. The LEDs ALARM1 and ALARM2 are lit.

Advertising