7  Grid Monitoring

User Manual

SCCP-JP-BA-A4-en-12

45

7 Grid Monitoring

7.1 How Grid Monitoring Works

The Sunny Central monitors the utility grid to make sure it stays within configurable thresholds. If the grid values exceed

or fall below these thresholds for a set time, the Sunny Central will disconnect from the utility grid for safety reasons.
The following thresholds are monitored:

• Voltage drop
• Voltage increase
• Frequency drop
• Frequency increase

For each threshold, you can set a tripping delay time stipulating how long the grid error must be pending before the

Sunny Central disconnects from the utility grid.

7.2 Setting Line Voltage Monitoring

You can specify the thresholds and tripping time manually. For voltage monitoring, you can set two limits for overvoltage

and two limits for undervoltage.
If the line voltage rises above the value defined in the parameters VCtlhhLim or VCtlhLim, the Sunny Central waits for

the period defined in the parameters VCtlhhLimTm or VCtlhLimTm and disconnects from the utility grid.

Figure 16: Temporal Sunny Central behavior when the grid limits are exceeded

Position

Parameters Description

A

VCtlhhLimTm Delay time for grid limit level 2

B

VCtlhLimTm

Delay time for grid limit level 1

C

Startup/MPP load operation

D

Grid monitoring

E

Disturbance

1

VCtlhhLim

Line voltage limit level 2