SMA SC 500CP-10-JP User Manual

Page 81

Advertising
background image

SMA Solar Technology AG

10  Troubleshooting

User Manual

SCCP-JP-BA-A4-en-12

81

10.4.5 Error Numbers 60xx to 90xx - Disturbance on the Sunny Central

Error no.

Explanation

Behavior of the

Sunny Central

Corrective measures

S 1

S 2

R

6002

Calibration data cannot be loaded.

Q

Q

• Contact the SMA Service Line.

6113

Data block cannot be loaded from

EEPROM or channel list has

changed (e.g. after firmware

update)

W

W

6115

Setting of hardware thresholds on

D/A converters not possible.

5 min

5 min

x

6116

Real-time clock not initialized.

W

W

6117

Device address not recognized.

5 min

5 min

x

6118

Parameter file invalid.

W

W

6119

Data structure for communication

between operation control unit and

digital signal processor invalid.

5 min

5 min

x

6120

Watchdog tripping error

30 s

W

6121

No response from watchdog

30 s

W

6122

Ten internal monitoring errors have

occurred in succession.

W

5 min

6123

Software runtime error

W

W

6128

Internal runtime error

5 min

5 min

x

6404

Overcurrent on line conductor L1,

L2 or L3

C

Q

x

6405

Overvoltage in the DC link of the

inverter bridge

30 s

5 min

6410

24 V voltage supply invalid

5 min

5 min

x

6417

15 V voltage supply invalid

5 min

5 min

x

6418

Overtemperature on the inverter

bridge detected

5 min

15 min

6422

Inverter bridge in undefined state

30 s

5 min

6423

Overtemperature detected in the

switch cabinet

5 min

30 min

6425

Synchronization error with

utility grid

30 s

5 min

x

6427

Sensor error of DC voltage

measurement

30 s

C

6440

Hermetic protection of transformer

no longer assured

30 s

5 min

• Check external transformer.