12  Parameters

User Manual

SCCP-JP-BA-A4-en-12

93

PF-WLockInVtg**

Power from which the

cos φ(P) characteristic

curve is activated, in %

relative to the nominal

voltage

0% to 110%

0%

PF-WLockOutVtg** Power from which the

cos φ(P) characteristic

curve is deactivated, in

% relative to the

nominal voltage

0% to 110%

0%

PF-WLockTm**

Waiting time for

activating or

deactivating the cos

φ(P) characteristic curve

0 s to 100 s

2 s

PwrMonErrMod

Mode used in the event

of communication

failure

LastVal

Use of last default values

received

LastVal

SubVal

Use of proxy values

PwrMonErrTm

Communication

downtime until proxy

values are used

1 s to 999 s

300 s

Q-EnaTmsVtg**

Activation of line

voltage delay in the

parameter

Q-VarTmsVtg

Off

Off

On

Q-VLockInW**

Voltage value from

which the Q(V)

characteristic curve is

activated, in % relative

to the nominal voltage

0% to 100%

0%

Q-VLockOutW**

Voltage value from

which the Q(V)

characteristic curve is

deactivated, in % based

on the nominal voltage

0% to 100%

0%

Q-VLockInTm**

Waiting time for

activation of Q(V)

characteristic curve

0 s to 100 s

2 s

Q-VLockOutTm**

Waiting time for

deactivation of Q(V)

characteristic curve

0 s to 100 s

2 s

Q-VArGraNom

Pos**

Reactive power

gradient at a positive

change of nominal

voltage

0%/V to 44.06%/V

SC 500CP-JP

0%/V

0%/V to 31.47%/V

SC 630CP-JP

0%/V to 25.04%/V

SC 800CP-JP

Name

Description

Value/range

Explanation

Default

value