10  Troubleshooting

SMA Solar Technology AG

84

SCCP-JP-BA-A4-en-12

User Manual

8704

External active and reactive power

setpoints invalid

W

W

• Contact the SMA Service Line.

9000

Power electronics self-test running

This message disappears once the

self-test is complete.

W

W

9008

Doors have been opened during

operation.

30 s

1 min

x

9009

Fast stop has been manually

tripped.

30 s

30 s

• Eliminate error and switch fast

stop back on.

9013

This is a grid stability shutdown (see

Section 3.8.7). The error is reset by

a signal from the grid operator or

from the safety system of the grid

interconnection point.

30 s

30 s

9019

Defective fast stop

30 s

Q

• Ensure that the fast stop is

correctly connected.

Error no.

Explanation

Behavior of the

Sunny Central

Corrective measures

S 1

S 2

R