7 alarms not indicated by alarm numbers – Yaskawa PC NC User Manual

Page 178

Advertising
background image

4 - 16

YASNAC PCNC Operating Manual

Chapter 4: Maintenance

This alarm occurs when the servo unit detects the alarm when the power is turned ON.

Motor insulation is faulty.

Contact your Yaskawa representative.

(23)Alarm No.: 3451 and 3452 (Follow-up Error)

This alarm occurs when the follow-up error exceeds the value set for the servo unit parameter.

The servo unit detects the alarm.

If this alarm occurs during axis feed over a long distance, it is necessary to either lower the

command speed or increase the gain.

If the motor does not rotate, the servo unit will be faulty.

Contact your Yaskawa representative.

4.1.7

Alarms Not Indicated by Alarm Numbers

(1) No Display is Given on the CRT

If nothing is displayed on the CRT, the CRT itself might be faulty or the display circuit or

connection cables might be faulty. When nothing is displayed even if the power can be
turned ON to the PCNC, check the cable connection to the operation panel and also the
connectors.

(2) Handle Mode Operation is Impossible

(a) Handle mode signal is not input

Check the bit status of UO monitor #3000.

D2 = 1

Other bits (DO, D1, D3 to D7) = 0

Check the mode display given in the normal display area on the screen.

(b) Axis selection signal is not input

I/O monitor

Check whether one of the following bits is ON.

#3070

D

0

= l

1st axis

D

l

= l

2nd axis

D

2

= 1

3rd axis

D

3

= 1

4th axis

D

4

= 1

5th axis