©2009 Magnum Energy Inc.

12

Operation

Table 3-2, Battery Combining Operation

4.0 Limitations of Throughput

The ME-SBC

TM

can allow charge currents from either battery to fl ow through

to the other battery (i.e. Main Battery to Auxiliary Battery or Auxiliary

Battery to the Main Battery). When the MOSFET turns on inside the ME-

SBC

TM

and the batteries are combined and a signifi cant inrush of current

occurs. This inrush may cause the ME-SBC

TM

to shutdown to protect itself or

reduce how much current it actually lets through to the other battery. If the

ME-SBC

TM

shutsdown to protect itself, it will restart in 10 Seconds and at-

tempt to recombine. If the ME-SBC

TM

reduces the output in order to maintain

a stable output, it will return to full output as soon as the average amperage

through the MOSFET lowers to a safe sustainable level.

note 1: When the ME-SBC

TM

is in the reduced output mode it only lets through

about 1/2 of the available amperage. It will continue to operate like this until

the total available Amps safely drops to a level the ME-SBC

TM

can conduct con-

tinuously. With a current probe, it may look like 50% of the rated output.

M ain

B attery B ank

A uxiliary (A U X)

B attery B ank

M E -S B C

S m art B attery C om biner

N e ga tiv e B us-ba r

Average Amps

Output Behavior

Status LED

0 - 25 Amps

Full output

Solid steady GREEN

26 - 30 Amps

in dial-back so as to

maintain some output.

1

Slow blink GREEN

>30 Amps

No output

Fast blink RED