6.0 Troubleshooting

Symptom

Solution

Not combining

Check Voltages at the Power Terminal Block. If

the Voltage #1 - MAIN POS (+) and #3 - COM

NEG (-) or #2 - AUX POS (+) and #3 - COM

NEG (-) are above the connect Voltage and the

difference between them is less the 10 VDC the

ME-SBC

TM

may be defective. Please call Magnum

(425) 353-8833.

No indicators

Check Voltages at the Power Terminal Block. If

the Voltage #1 - MAIN POS (+) and #3 - COM

NEG (-) or #2 - AUX POS (+) and #3 - COM

NEG (-). The Voltage between 1 and 3 or 1 and 2

must be more than 5VDC.

Not Disconnecting

ME-SBC

TM

does not disconnect. Remove the fuse

at both batteries and check resistance at #1

- MAIN POS (+) and #2 - AUX POS (+) on the

ME-SBC

TM

. There should be about 600k Ohms (Ω).

If there isn’t the ME-SBC

TM

might be defective.

Please call Magnum (425) 353-8833

Auto Reconnecting

every 10 Sec

If the Voltage requirements are satisfi ed and

this cycling occurs, then the Current sensing

is corrupt or the Current exceeds continuous

capabilities. Wait for the charger to go into Float

Mode and check status again. If the ME-SBC

TM

is

still toggling it may be defective, otherwise it’s

probably operating normally and protecting itself.

Adjustments are

unresponsive

Turn the knobs fully counterclockwise until they

stop and then adjust up to the setting. If they

don’t stop or don’t move call Magnum.

Table 6-1, Troubleshooting table