Empire Products GWT-35-2(SG User Manual

Page 8

Advertising
background image

12425-10-1008

Page 8

1. In selecting a location for installation, it is necessary to provide

adequate accessibility clearances for servicing and proper

installation.

2. Clearances to combustible surfaces are 4" (102mm) from sides,

12" (305mm) to top, 1 1/2" (38mm) from floor.

Wall furnaces shall be installed in a location in which the facilities

for ventilation permit satisfactory combustion of gas and proper

venting under normal conditions. In buildings of conventional

frame, brick, or stone construction without tight storm windows

and doors, infiltration is normally adequate to provide air for

combustion and draft hood dilution.

Where appliances are installed in confined and unconfined spaces

within a building, the building being of unusually tight construction,

air for combustion and ventilation must be obtained directly from

outdoors or from such spaces that freely communicate with the

outdoors. Under these conditions, the confined and unconfined

spaces shall be provided with two permanent openings, one near

the top of the enclosure and one near the bottom; each opening

shall have a free area of not less than one square inch (6.45cm

2

)

per 2,000 BTU (.6KW/H) per hour of total input.

Select a location near the center of the space to be heated. Overflow

heat will circulate through doorways into adjacent rooms.
For large homes or spread-out floor plans, two or more furnaces are

recommended. Do not locate furnace where a door could swing

over the outer casing, or where circulation could be retarded by

furniture or cabinets.
Do not install in a closet, alcove or small hallway where the furnace

could be isolated by closing doors to the heated space.

When location is selected, check the walls, attic and roof to make

sure there are no obstructions such as pipes, electric wiring, etc.,

which would interfere with the installation of the furnace or vent

pipe.
NOTE: If Rear Register Kit is to be used, see Rear Register Kit

instructions for location of hole in rear wall. Register

outlet must be cut in wall before furnace is installed.

NOTE: If Optional Blower is to be used, hard wiring must be

completed for the optional blower prior to installation of

header plate.

Provide an opening in the wall 14 1/2" (368mm) wide and 66

1/8" (168cm) high measured from top of floor plate (See Figure

2 and Figure 3). Wall depth is to be 2" x 4" framing with 1/4"

(6.5mm) to 5/8" (16mm) sheeting. Attach baseplate (not supplied

with furnace) to header plate with sheet metal screws at each end.

Attach 4" (102mm) oval, double wall vent pipe to baseplate. Attach

enough vent pipe so that when installed in wall opening the vent

pipe will extend above the ceiling plate by at least 6" (152mm).

Install ceiling spacers according to manufacturer's instructions.

Insert header plate with attached 4" oval, double wall vent pipe

into wall opening. Position header plate at height shown in Figure

2. Locate rear edge of nailing flange at the back of the 2" x 4" stud

which will center the vent collar in the wall. Locate the angled edge

of header plate flush with the top of the wall opening. Nail header

plate to the wall studs.

NOTE: Minimum distance of 1 1/2" (38mm) must also be

maintained from top surface of carpeting, tile, etc.

CLEARANCES

VENTILATION AND COMBUSTION AIR

LOCATION - ALL MODELS

ROUGH-IN INSTRUCTIONS