1.3.11 External Alarm Circuits: Nine (9) Form-C alarm relay contacts are provided and

mapped by the MCA as detailed in the following table. Alarm relay contacts are rated
for 0.5A at 125VAC, 1.0A at 30VDC, and 0.3A at 110VDC. Relay operation can be tested via an
Alarm Relay Test feature. When activated, this feature consecutively places each relay in the
alarm state for the programmed time period.

• Refer to the "Making Electrical Connections" chapter of the Power System Installation

Instructions (Section 6012) for connection details.

• Refer to the "Navigating the MCA" and "System Operating Procedures" chapters of the

Power System User Instructions (Section 6013) for alarm conditions. Additional descriptions
are provided in a) and b) below.

a) MCA

Audible

Alarm: These contacts change state if any alarm condition monitored by

the MCA occurs, and are provided for connection to an audible alarm circuit.

b) Test/Equalize

Indication: These contacts change state if the system is placed in the

test/equalize mode, locally or remotely.

Power System

List No.

10 11 12 13

MCA

Configuration

No.

534876 534877 534878 534879

Relay K1

Major

Alarm

Major

Alarm

Major

Alarm

Major

Alarm

Relay K2

Minor

Alarm

Minor

Alarm

Minor

Alarm

Minor

Alarm

Relay K3

High

Voltage 1

Alarm

High

Voltage 1

Alarm

High

Voltage 1

Alarm

Test/EQ

Mode

Indication

2

Relay K4

High

Voltage 2

Alarm

Rectifier

Module

Fail Major

Alarm

MCA

Fail

Alarm

Fuse

Alarm

Relay K5

Battery

On

Discharge

Alarm

Battery

On

Discharge

Alarm

Battery

On

Discharge

Alarm

Battery

On

Discharge

Alarm

Relay K6

50%

Battery

On

Discharge

Alarm

Rectifier

Module

Fail

Minor

Alarm

Very Low

Voltage

Alarm

AC

Major

Alarm

Relay K7

AC

Fail

Alarm

AC

Fail

Alarm

AC

Fail

Alarm

AC

Fail

Alarm

Relay K8

Audible

Alarm

Audible

Alarm

Fuse

Alarm

LVD

Alarm

Relay K9

Test/EQ

Mode

Indication

Fuse

Alarm

Rectifier

Module

Fail

Alarm

Test/EQ

Mode

Indication