SAG581126000

System Application Guide

Issue AD, November 23, 2009

Spec. No. 581126000 (Model 700

NVBA

)

Page 118 of 123

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Connections to Inter-bay Busbars (P/O List 2)

Note: Battery busbars within distribution cabinets are rated for 2000A max.

For 2000A-4000A in List 2, make battery connections to inter-bay busbars, shown here.

DETAIL A

1"

2-3/8"

2-3/8"

2-3/8"

5/8"

3/4"

3/4"

3/4"

1-5/8"

1-5/8"

3/8-16 CAPTIVE NUT, 8 PLACES PER BUS
(CUSTOMER MUST PROVIDE LUG BOLTS
AND ADDITIONAL HARDWARE. BOLT LENGTH: 1-1/4")

1/4-20 CAPTIVE NUT, 12 PLACES PER BUS

(CUSTOMER MUST PROVIDE LUG BOLTS

AND ADDITIONAL HARDWARE. BOLT LENGTH: 1-1/4")

13/16"

13/16"

13/16"

13/16"

GND RETURN
Interbay Busbar Assembly

+24V SUPPLY
Interbay Busbar Assembly

Battery Lug

Landing Points

See Detail A

Rear View