System Application Guide

SAG581126000

Spec. No. 581126000 (Model 700

NVBA

)

Issue AD, November 23, 2009

Page 31 of 123

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Manufacturer* Model

Emerson

Network

Power

P/N

Rated 8-Hr.

Capacity

(Ah)

Dimension

W x L x H

(Inches)

Required

Tray

Spacing

Weight

per

battery

(lbs)

C&D

TEL12-160F

140456

157

4.95 x 22.01 x 11.14

7U

115

C&D

TEL12-180F

--

181

4.95 x 22.01 x 12.60

8U

131

Deka Unigy I

12AVR-150ET

122018

150

4.90 x 22.00 x 11.75

8U

115

Douglas

DGS12-150F

125453

150

4.90 x 22.00 x 12.70

8U

137

Douglas

DST12-170F

--

170.8

4.92 x 22.05 x 12.60

8U

129.6

Enersys

PowerSafe

12V155F

122010

155

4.92 x 22.09 x 12.44

8U

148

Fiamm

12FAT125

--

125

4.96 x 21.97 x 10.67

7U

110.23

Fiamm

12FAT155

--

155

4.96 x 21.97 x12.64

8U

132.25

GNB Marathon

M12V125FT

--

125

4.90 x 22.00 x 11.15

7U

105

GNB Marathon

M12V155FT

112795

155

4.90 x 22.00 x 11.15

7U

119

Northstar

NSB170FT

--

167

4.92 x 22.05 x 12.60

8U

131

* See

Battery Manufacturer Information

located at the end of this document.

3) Specify rack spacing of 7U (12.25”) or 8U (14”) between trays and above top tray as required for battery

clearance. See table above.

4) Specify the batteries you intend to use with each List 93 ordered. Lugs for battery connections vary

according to the batteries to be installed. Battery cables will be lugged as shown in the following table.
The table is provided for reference only.

Battery Lug Kit Part Numbers

(Kit provides two lugs for one tray.)

Battery

Specified

Ordered Without

Circuit Breaker

Ordered With

Circuit Breaker

125A or Higher

Ordered With

Circuit Breaker

100A or Lower

C&D TEL12-160F

528235

528235

528234

C&D TEL12-180F

528235

528235

528234

Deka Unigy I 12AVR-150ET

528235

528235

528234

Douglas DG

S12-150F

528237 528237 528236

Douglas DST12-170F

528235

528235

528234

Enersys PowerSafe 12V155F

528235

528235

528234

Fiamm 12FAT125

528235

528235

528234

Fiamm 12FAT155

528235

528235

528234

GNB Marathon M12V125FT

528235

528235

528234

GNB Marathon M12V155FT

528235

528235

528234

Northstar NSB170FT

528235

528235

528234

5) Specify with or without Battery Disconnect circuit breakers. Note: All List 93 trays in a bay will be

furnished with or without Battery Disconnect circuit breakers as specified for the first tray ordered.