List AC: Distribution Bus Module (P/N 507198)
(3) GJ/218 Circuit Breaker System Positions

Features

♦ Single Voltage Distribution (+24V)
♦ 500A Maximum Capacity
♦ (3) Load Distribution Circuit Breaker Mounting Positions

(100 to 600A GJ/218-Type) NOTE RESTRICTIONS

Restrictions

For use in a 4-bus row cabinet only. Must be installed in bus position D (row 4). See also

List AB

for similar

application in bus positions A-C (rows 1-3).

Panel is designed to mount circuit breakers in the following possible combinations:

(3) 100A to 250A
(1) 100A to 250A and (1) 300A or 400A
(1) 600A

Ordering Notes

1) Order circuit breakers and associated jumper kits as required per Tables

5

and

6

.

2) Order load lugs (two hole, 3/8” bolt clearance hole, 1” centers) as required for each distribution position

per Table

10

.

1"

1.5"

1"

1"

LOADS

1"

LOAD

CONNECTIONS

GROUND

BUSBAR

LOAD RETURN

CONNECTIONS

3/8-16 CAPTIVE NUT, 12 PLACES
(CUSTOMER MUST SUPPLY LUG
BOLTS AND ADDITIONAL
HARDWARE. BOLT LENGTH: 1-1/4")