System Application Guide

SAG581126000

Spec. No. 581126000 (Model 700

NVBA

)

Issue AD, November 23, 2009

Page 87 of 123

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Recm 90

°C Wire Size

(1)

4 AWG

2 AWG

1/0 AWG

2/0 AWG

3/0 AWG

4/0 AWG

250

kcmil

350

kcmil

Fuse/

Circuit

Breaker

Amperage

Loop Length (feet)

(2)

90A

41

(3)

66

(3, 4)

105

(3, 4)

133

(4)

-- -- -- --

100A

-- 59

(3, 4)

95

(3, 4)

119

(3, 4)

-- -- -- --

125A

-- 47

(3)

76

(3, 4)

95

(3, 4)

120

(4)

-- -- --

150A

-- --

63

(3, 4)

79

(3, 4)

100

(3, 4)

-- -- --

200A

-- -- -- --

75

(3, 4)

95

(3, 4)

112

(3, 4)

--

250A

-- -- -- -- --

76

(3, 4,

7)

90

(3, 4,

7)

126

(3, 4,

7)

Recommended Crimp Lug

Lug

(5)

245346800 245346900

245393500

(6)

245393600

(6)

245393700

(6)

245393800

(6)

514872

(6)

514873

(6)

Lug

(8, 9)

--

245348200 245347100 245347200 245347300 245347400 245347500 245347700

1

Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved

National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for copper
wire at 90°C conductor temperature operating in ambients of 30

°C and 40°C was used. For other operating

ambient temperatures, refer to the NEC. For operation in countries where the NEC is not recognized,
follow applicable codes.

2

Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less at listed branch current for

the loop lengths shown. Loop length is the sum of the lengths of the positive and negative leads.

3

Wire Size / Loop Length Combination Calculated using 30°C Ambient Operating Temperature.

4

Wire Size / Loop Length Combination Calculated using 40°C Ambient Operating Temperature.

5

Two-hole lug, 1/4" bolt clearance hole, 5/8" centers. Refer to drawing 031110100 for lug crimping

information.

6

Special application crimp lug / strap combination.

7

MUST USE P/N 514717 Lug Adapter Busbar for lugs having 1/4" bolt clearance hole, 5/8" centers.

8

Two-hole lug, 3/8" bolt clearance hole, 1" centers. Refer to drawing 031110100 for lug crimping

information.

9

MUST USE P/N

534449

Lug Adapter Busbar Kit for 125-200A circuit breakers or P/N

514714

Lug

Adapter Busbar Kit for 250A circuit breakers.

Table 12 (cont'd from previous page)

Recommended Wire Sizes and Lugs for Load and Battery Connections

to Various TPS/TLS Fuses and Bullet Nose-Type Circuit Breakers

or Battery Branch Circuits