Flue – MCZ Forma Wood 75 Dx - mod.2012 User Manual

Page 15

Advertising
background image

13

4-FLUE

Technical Dept. - All rights reserved - Reproduction is prohibited

For stoves installed in studio flats, bedrooms and bathrooms (where allowed), it is mandatory to connect the combustion air outside. In

particular for sealed products the connection must be sealed in order not to compromise the overall sealed characteristic of the system.

DISTANCE (metres)

The air inlet must be at a distance of:

1.5 m

UNDER

Windows, doors, smoke outlets, cavities, ....

1.5 m

HORIZONTALLY

Windows, doors, smoke outlets, cavities, ....

0.3 m

ABOVE

Windows, doors, smoke outlets, cavities, ....

1.5 m

AWAY

from smoke outlet

CONNECTION TO FLUE

The connection between the flue and the appliance must be via a smoke duct that conforms with EN 1856-2. To connect the fireplace to

the chimney flue or to a ceiling connection that is not coaxial to the unit’s smoke outlet, changes of direction must be made using open

bends no greater than 45° with respect to the vertical.

For stoves the connecting section to the flue must extend no more than 2 m horizontally, with a minimum slope of 3% and with a

maximum of 3 90° bends (accessible for inspection - do not count the T fitting at the unit outlet).

The diameter of the smoke duct must be equal to or greater than that of the appliance outlet. A possible increase/reduction of the cross-

section is only allowed when the flue is connected (in particular the reduction must be confirmed by an adequate system size calculation).

EXAMPLE OF HYDRO FIREPLACE FITTING

A. CERAMIC FIBRE INSULATION

B. SMOKE FITTING

C. CHIMNEY FLUE

D. HOOD GRILLE

TYPICAL DIAGRAM OF A CORRECTLY LAID CHIMNEY FLUE

WITH, AT THE FOOT OF THE EXTERNAL RISING SECTION, THE

POSITIONING OF A CHAMBER WITH A SEALED HATCH TO

COLLECT AND REMOVE THE SOLID MATERIALS PRODUCED

DURING COMBUSTION.

Advertising