2-INSTALLATION INSTRUCTIONS

CHIMNEYPOT

Often, if this factor is underestimated it hinders smooth “chimney system” operation.

The draught of the chimney also depends on its chimneypot.

In the case of an artisan product, it is very important for the four expulsion sections to be more than twice the internal section of

the chimney.

The chimneypot will be exposed to the four winds and it is therefore recommended for it to be specifically designed to

withstand the elements (e.g. an industrial chimney).

INDUSTRIAL CHIMNEYPOT WITH
PREFABRICATED STACKED ELEMENTS. ALLOWS
EXCELLENT SMOKE EXPULSION.

TRADITIONAL ARTISAN CHIMNEYPOT.
THE CORRECT EXPULSION SECTION MUST BE AT
LEAST TWICE THE INTERNAL SECTION OF THE
CHIMNEY; IDEALLY 2.5 TIMES ITS SIZE.

CHIMNEYPOT FOR A STEEL CHIMNEY WITH
AN INTERNAL CONE AND SMOKE DEFLECTOR.
ALLOWS EXCELLENT SMOKE EXPULSION.

The chimneypot must comply with the following requirements:

• Have an internal section equal to that of the chimney.

• Have a useful outlet section that is at least double that of the internal section of the chimney.

• Be constructed in such a way so as to prevent rain, snow and any foreign body from entering the chimney.

• Be positioned so as to ensure adequate smoke dispersion and in any case beyond the reflux area in which counter pressure is likely

to form.

YES
A) UPPER STOREY OR SOLID
COMBUSTIBILITY.
B) LOWER STOREY.

NO