2-INSTALLATION INSTRUCTIONS

In the case of paired chimneys, the solid combustibility or upper storey chimneypot must be at least 50 cm higher than the

others in order to prevent the pressure from being transferred between the paired chimneys.

The chimneypot must not have any obstacles within a range of 10 metres, such as walls, slopes and trees. In this case, raise

it at least 1 m above the obstacle and in the case of other chimneypots nearby, leave a gap of at least 2 m. In any case, the

chimneypot must exceed the highest point of the roof by at least 1 m or be above the reflux area, which is equal to 130 cm

in roofs with a gradient greater than 10° (perpendicular height to the surface of the roof).