Roblem solving – Riello UPS Sentinel Dual (High Power) (3.3 - 10 kVA) User Manual

Page 61

Advertising
background image

61

P

ROBLEM SOLVING

PROBLEM

POSSIBLE CAUSE

SOLUTION

THE BUZZER SOUNDS

CONTINUOUSLY AND THE

DISPLAY POSTS ONE OF

THE CODES: A54, F50, F51,

F52, F55, L50, L51, L52

THE LOAD APPLIED TO THE

UPS IS TOO HIGH

Lower the load to inside the 100% threshold (or user
threshold in case of code A54).

THE DISPLAY SHOWS

CODE: A61

BATTERIES NEED TO BE

REPLACED

Replace the battery pack with a new one (as indicated in
the chapter BATTERY PACK).

THE DISPLAY SHOWS

CODE: A62

BATTERY PACK MISSING

OR NOT CONNECTED

Check that the battery pack is inserted and connected
correctly (see the chapter BATTERY PACK).

THE DISPLAY SHOWS

CODE: A63

BATTERIES ARE

DISCHARGED; THE UPS IS

WAITING FOR THE

BATTERY VOLTAGE TO

EXCEED THE SET

THRESHOLD

Wait for the batteries to recharge or manually force
switching-on by holding the “ON” button down for at
least 2 sec.

THE BUZZER SOUNDS

CONTINUOUSLY AND THE

DISPLAY POSTS ONE OF

THE CODES: F03, F05, F07,

F10, F13, F21, F40, F41, F42,

F43

A UPS MALFUNCTION IS

TAKING PLACE;

SHUTDOWN IMMINENT

If it is possible to power down the load, switch off the
UPS and switch it on again; if the problem occurs again,
contact the service centre.

THE BUZZER SOUNDS

CONTINUOUSLY AND THE

DISPLAY POSTS ONE OF

THE CODES: F04, L04

TEMPERATURE OF THE

HEAT SINKS INSIDE THE

UPS IS TOO HIGH

Check that the UPS surrounding ambient temperature is
not in excess of 40°C.

THE BUZZER SOUNDS

CONTINUOUSLY AND THE

DISPLAY POSTS ONE OF

THE CODES: F53, L53

FAULT DETECTED ON ONE

OR MORE LOADS POWERED

BY THE UPS

Disconnect all the loads and connect them up again one
by one to identify the faulty one.

THE BUZZER SOUNDS

CONTINUOUSLY AND THE

DISPLAY POSTS ONE OF

THE CODES: F60, L03, L05,

L07, L10, L13, L20, L21,

L40, L41, L42, L43

A UPS MALFUNCTION HAS

OCCURRED

If it is possible to power down the load, switch off the
UPS and switch it on again; if the problem occurs again,
contact the service centre.

THE DISPLAY SHOWS ONE

OF THE CODES: C01, C02,

C03

A REMOTE COMMAND IN

PROGRESS

If undesired, check the position of the manual bypass
switch or status of the control inputs of an optional
contacts card.

Advertising