ROBLEM SOLVING

A

LARM CODES

By using a sophisticated self-test system, the UPS can check and report on the display panel any problems
and/or failures that could occur during normal operation of the equipment. In case of a problem, the UPS
signals the event by posting on the display the code and type of alarm present (FAULT and/or LOCK).

FAULT

The FAULT type reports may be divided into three categories:

Failures: these are “minor” problems that do not result in the UPS stopping but they limit its

performance or prevent certain features being used.

CODE

DESCRIPTION

A06

Temperature sensor1 less than 0°C

A08

Temperature sensor2 less than 0°C

A11

Input relay stuck (does not open)

A54

ON LINE: load > of the user threshold - ECO: load > 16A *

A61

Batteries need replacement

A62

Battery pack missing or not connected

A63

Waiting for batteries to recharge


Alarms: these problems are more critical than the failures because – if they continue – they could

cause the UPS to stop, even in a very short time frame.

CODE

DESCRIPTION

F03

Auxiliary power supply incorrect

F04

High temperature on heat sinks

F05

Temperature Sensor1 broken

F07

Temperature Sensor2 broken

F10

Input fuse broken or input relay stuck (does not close)

F13

Capacitor precharging failure

F21

Capacitor bank overvoltage

F40

Inverter overvoltage

F41

D-C voltage on output

F42

Inverter voltage not right

F43

Inverter undervoltage

F50

Overload: load > 103%

F51

Overload: load > 110%

F52

Overload: load > 150%

F53

Short-circuit

F55

Waiting for load reduction before return to inverter

F60

Battery overvoltage