ECHNICAL DATA TABLE

OVERLOAD TIMES

OPERATION POWERED BY

BYPASS

INVERTER

100% < Load 110%

Activates bypass after 2 sec

Stoppage after 120 sec

Stoppage after 60 sec

110% < Load 150%

Activates bypass after 2 sec

Stoppage after 4 sec

Stoppage after 4 sec

Load > 150%

Activates bypass instantaneously

Stoppage after 1 sec

Stoppage after 0.5 sec



(1)

@ nominal load, minimum voltage of 164 Vac, battery charging

(2)

@ nominal load, nominal voltage of 230 Vac, battery charging

(3)

Mains/Battery @ load 0% -100%

(4)

@ Mains/battery/mains @ resistive load 0% / 100% / 0%

(5)

If the mains frequency is within ± 5% of the value selected, the UPS is synchronized with the mains. If the
frequency is outside the tolerances or operation is battery-powered, the frequency is the selected frequency +0.1%

(6)

20 - 25 °C for longer battery life

(7)

To maintain the output voltage inside the precision range indicated, a recalibration may be necessary after a long
period in operation




When using a RS232 or USB communication cable to reduce EMI interference fit the ferrite supplied with
the UPS as follow:

1) Open the clip;
2) Place the ferrite as close as possible to the connector on the UPS side;
3) Place the communication cable inside ferrite groove with a turn (see figure);
4) Close the clip with communication cable inside (the cable must be remain in the ferrite hole).