ROBLEM SOLVING

Commands in progress: Indicates presence of a remote command in progress.

CODE

DESCRIPTION

C01

Remote shutdown command

C02

Remote load on bypass command

C03

Remote switch-on command

C04

Battery test in progress



LOCK

The LOCK (block) type report signals are usually preceded by an alarm signal and, on account of their
importance, result in the inverter being switched off and the load being powered through the bypass line (the
procedure is excluded in case of lockouts due to strong and persistent overloads and lockouts following a
short-circuit).

CODE

DESCRIPTION

L03

Auxiliary power supply incorrect

L04

High temperature on heat sinks

L05

Temperature Sensor1 broken

L07

Temperature Sensor2 broken

L10

Input fuse broken or input relay stuck (does not close)

L13

Capacitor precharging failure

L20

Capacitor bank undervoltage

L21

Capacitor bank overvoltage

L40

Inverter overvoltage

L41

D-C voltage on output

L42

Inverter voltage not right

L43

Inverter undervoltage

L50

Overload: load > 103%

L51

Overload: load > 110%

L52

Overload: load > 150%

L53

Short-circuit


* In ECO mode, the load is normally powered by the bypass. Therefore, in the presence of a load of constant power,

the current absorbed depends on the mains voltage, which may accordingly be in excess of the value allowed by the
input plug and the protection upstream.
When this situation arises, the UPS reports a failure which automatically disappears if the input voltage increases
and/or the output load is reduced.