1 [module – ProSoft Technology MVI94-MCM-MHI User Manual

Page 20

Advertising
background image

Configuration

MVI94-MCM ♦ Flex I/O Platform

User Manual

Serial Communications Modbus Communication Module

Page 20 of 109

ProSoft Technology, Inc.

March 29, 2011

3.1

[Module]

[Section]/Item

Value

Range

Description

[Module]

Configuration header for Module.

Module Name:

Up to 80

chars

Name of the module to use on reports. Use this

parameter to identify your module in your system.

Maximum Register:

1 to 3996

This parameter defines the maximum register in
the virtual Modbus database. You should size the

database for your application, leaving room for

expansion in the future. Requests for registers
outside of the range selected are returned with an

error message.

Error/Status Block

Pointer:

-1 to 3995

This value represents the relative starting position
in the module's internal Modbus database where

the Error/Status data is stored. The table can be

placed anywhere in the module's data space. The
content of the Error/Status table is updated at the

frequency defined in the following parameter. If a

value of -1 is set for the parameter, the data is not

placed in the database.

Error/Status

Frequency:

0 to 65535

This parameter specifies the number of program
cycles between each update of the Error/Status
block data in the module. If the parameter is set to

a value of 0, the data is never updated.

BT Read Start

Register:

0 to 3995

This parameter specifies the starting register in
the internal Modbus database to write over the

backplane.

BT Read Register

Count:

12 to 3996

This parameter specifies the number of registers
in the internal Modbus database to write over the

backplane. This parameter computes the number
of blocks to transfer from the module to the

backplane. The number of blocks must be >=2 for

proper backplane data transfer.

BT Write Start

Register:

0 to 3995

This parameter specifies the starting register in
the internal Modbus database to fill with data read

over the backplane.

BT Write Register

Count:

12 to 3996

This parameter specifies the number of registers
in the internal Modbus database to consider from

the read operations over the backplane. This
parameter computes the number of blocks to

transfer from the backplane to the module. The

number of blocks must be >=2 for proper

backplane data transfer.

Backplane Fail

Count:

0 to 65535

This parameter specifies the number of
consecutive backplane transfer failure before
communications is disabled. If the parameter is

set to a value of 0, communications is not

disabled.