3.3

[Modbus Master]

The [Modbus Master] section of the configuration file defines the command list

specifications for the master port. The following table describes the parameters

defined in this section:

[Modbus Master]

Configuration header for Modbus Master.

Command Count:

0 to 100

This parameter specifies the number of
commands to be processed by the Modbus

Master port.

Minimum Command

Delay:

0 to 65535

This parameter specifies the number of
milliseconds to wait between issuing each

command. This delay value is not applied to

retries.

Command Error

Pointer:

-1 to 3995

This parameter sets the address in the internal
Modbus database where the command error data
is placed. If the value is set to -1, the data is not

transferred to the database.

Response Timeout:

0 to 65535

This parameter represents the message response
timeout period in 1 mSec increments. This is the

time that a port configured as a master will wait

before re-transmitting a command if no response

is received from the addressed slave. The value is
set depending upon the communication network

used and the expected response time of the

slowest device on the network.

Retry Count

0 to 10

This parameter specifies the number of times a

command will be retried if it fails.

Error Delay Count

0 to 65535

This parameter specifies the number of polls to
skip on the slave before trying to re-establish

communications. After the slave fails to respond,
the master will skip commands to be sent to the

slave the number of times entered in this

parameter.