MVI94-MCM ♦ Flex I/O Platform

Reference

Serial Communications Modbus Communication Module

User Manual

ProSoft Technology, Inc.

Page 75 of 109

March 29, 2011

5.3.3 Data Transfer

Data is transferred over the backplane using the module’s input and output

images. The module is configured with an eight-word input image and a seven-

word output image. The module and the processor use these images to page

data and commands. The input image is set (written) by the module and is read

by the processor. The output image is set (written) by the Flex processor and

read by the module. The following diagram shows this relationship.

The module’s program is responsible for setting the block identification code

used to identify the data block written and the block identification code of the

block it wants to read from the processor. User configuration information

determines the read (BT Read Start Register) and write (BT Write Start Register)

locations in the virtual Modbus database and the amount of data transferred (BT

Read Register Count and BT Write Register Count). Each read and write

operation transfers a six-word data area. The read operation (from the processor

to the module) contains a two-word header that defines the block identification

code of the read data and the block identification code of the next write block

requested. These identification codes are in the range of 0 to 666. A value of

zero indicates that the block contains no data and should be ignored. The first

valid block identification code is one and refers to the first block of six words to

be read or written.