5.5

Configuration Form

This section contains configuration forms that will aid in the configuration of the

module. If you design your system before trying to directly implement it, you will

have a greater chance of success. Fill in the configuration form for your

application, then edit the configuration text file.

[Section]/Item

Value

Range

Description

[Module]

Configuration header for Module.

Module Name:

Up to 80

chars

Name of the module for use on reports. Use this parameter to

identify your module in your system.

Maximum

Register:

1 to 3996 This parameter defines the maximum register in the virtual

Modbus Database. You should size the database for your

application leaving room for expansion in the future.

Requests for registers outside of the range selected will be

returned with an error message.

Error/Status Block

Pointer:

-1 to 3995 This value represents the relative starting position in the

module's internal Modbus database where the Error/Status

data will be stored. The table can be placed anywhere in the

module's data space. The content of the Error/Status table is

updated at the frequency defined in the Error/Status
Frequency. If a value of -1 is set for the parameter, the data

will not be placed in the database.

Error/Status

Frequency:

0 to

65535

This parameter specifies the number of program cycles
between each update of the Error/Status Block data in the

module. If the parameter is set to a value of 0, the data is

never updated.

BT Read Start

Register:

0 to 3995 This parameter specifies the starting register in the internal

Modbus database to write over the backplane.

BT Read Register

Count:

12 to

3996

This parameter specifies the number registers in the internal
Modbus database to write over the backplane. This

parameter computes the number of blocks to transfer from
the module to the backplane. The number of blocks must be

>= 2 for proper backplane data transfer.

BT Write Start

Register:

0 to 3995 This parameter specifies the starting register in the internal

Modbus database to fill with data read over the backplane.

BT Write Register

Count:

12 to

3996

This parameter specifies the number registers in the internal
Modbus database to consider from the read operations over

the backplane. This parameter computes the number of

blocks to transfer from the backplane to the module. The
number of blocks must be >= 2 for proper backplane data

transfer.

Backplane Fail

Count:

0 to

65535

This parameter specifies the number of consecutive
backplane transfer failures before communications is

disabled. If the parameter is set to a value of 0,

communications is not disabled.

Type:

0, 1, 3, 4

This parameter specifies if the port will emulate a Modbus
master device (0), a Modbus slave device without pass-
through (1), a Modbus slave device with pass-through and

data swapping (3), or a Modbus slave device with pass-

through (4).