The module and the processor constantly monitor input and output images. How

does either one know when a new block of data is available? Recognizing a

change in the header information of the image (word 0) solves the problem. For

example, when the module recognizes a different value in the first word of the

output image, new data is available from the processor. When the processor

recognizes a new value in the first word of the input image, new data is available

from the module. This technique requires the storage of the previously processed

data block identification code. The following illustration shows the normal

sequence of events for data transfer:

The steps outlined in the diagram above are discussed below:
1 During program initialization, the write and read block identification codes are

set to one. The last block read variable is set to zero.

2 The program copies the first six-word block of the virtual Modbus database

starting at the user defined BT Read Start Register to the input image (words

2 to 7). It then sets the current read block code in word 1 of the input image.

To "trigger" the write operation, the program places the current write block

code into word 0 of the input image.

3 The Flex processor recognizes a new value in word 0 of the input image

(based on the last_read_block_code not equal to read_block_code) in its

ladder logic. The ladder logic computes the offset into the file based on the

following formula: