Connection Parameters

13.

Set the module’s Requested Packet Interval (RPI). This is how often
the module’s scheduled data is updated in the processor. The value
can range from 5.0 to 3200.0 ms.

14.

Click Finish >> to complete the module configuration.

Configuring Input-Only Connections

In a ControlLogix system, multiple processors can receive inputs from a
module. Only one processor can control the outputs. To configure an
input-only connection to the AN-X module:

1.

Right click on I/O configuration and select New Module…

2.

Select a module of Type 1756-ETHERNET, Description Generic
Ethernet Module from the list and click OK. RSLogix 5000 displays
the Module Properties dialog box.