ProSoft Technology AN-X-PB User Manual

Page 32

Advertising
background image

Page

26

AN-X-PBSLV

January 2008

3.

Assign the module a Name and optionally a Description.

4.

Set the Comm Format to Input Data – INT – With Status (or Input
Data – INT).

5.

Set the IP Address to match the IP address of the AN-X module.

6.

Set the Input Assembly Instance to 1. Normally you set the size to
the maximum allowed, 250 words. You can set it to a smaller value
but it should be large enough to transfer all the mapped data. If there
is also an exclusive owner connection, then the size should match the
exclusive owner size.

7.

Set the Output Assembly Instance to be 3. You cannot set the size.

8.

Set the Configuration Assembly Instance to 4. Set the size to 0.

9.

Set the Status Input Assembly Instance to 5. Normally you set the
size to the maximum allowed, 250 words. You can set it to a smaller
value but it should be large enough to transfer all the mapped data. If
there is also an exclusive owner connection, then the size should
match the exclusive owner size.

10.

Set the Status Output Assembly Instance to 6. You cannot set the
size.

11.

Click Next > to display the second Module Properties dialog box.