Parameters, Installation and operations manual – Heatcraft Refrigeration Products PRO3 User Manual

Page 10

Advertising
background image

10

Installation and Operations Manual

Parameters

Label

Characteristic

Description

Menu/User

Level

Possible

Settings

DEFAULT SETTINGS

Low

Temp.

Medium

Temp.

High

Temp.

REgULATION

SEt

Set Point

LS ~ US

-10

34

38

Hy

Differential

(0,1 ÷ 5,5°C / 1÷55 °F) Intervention

differential for set point. Compressor

Cut IN is Set Point + differential (Hy).

Compressor Cut OUT is when the

temperature reaches the set point

Pr1

1~ 45

3

3

3

LS

Minimum set point (- 50°C÷SET/-58°F÷SET): Sets the

minimum value for the set point..

Pr

-67 ~ SET

-3

5

33

US

Maximum set point (SET÷110°C/ SET÷30°F). Set the

maximum value for set point.

Pr

SET ~ 30F

37

40

45

Ot

Thermostat probe

calibration

(-1.0÷1.0°C; -10÷10°F) allows

to adjust possible offset of the

thermostat probe

Pr

-1~1

0

0

0

OdS

Outputs activation

delay at start up

(0÷55min) This function is

enabled at the initial start up of the

instrument and inhibits any output

activation for the period of time set in

the parameter

Pr

0 ~ 55

minutes

0

0

0

AC

Anti-short cycle

delay

(0÷50 min) minimum interval

between the compressor stop and

the following restart

Pr

0 ~ 50 minutes

4

4

4

COF

Compressor OFF

time with faulty

probe

(0÷55 min) time during which the

compressor is OFF in case of faulty

thermostat probe. With COF=0

compressor is always active

Pr

0 ~ 55

minutes

6

6

6

DISPLAY

CF

Temperature

measurement unit

°C=Celsius; °F=Fahrenheit. WARNING:

When the measurement unit is

changed the SET point and the values

of the parameters Hy, LS, US, Ot, ALU

and ALL have to be checked and

modified if necessary

Pr

°C = Celsius

°F =Fahrenheit

°F

°F

°F

DEFROST

tdF

Defrost type

EL = electrical heater; in = hot gas

Pr

EL = electric

defrost / in =

hot gas defrost

EL

EL

EL

dtE

Defrost termination

temperature

(-50÷50 °C/ -58÷1°F) (Enabled only

when EdF=Pb) sets the temperature

measured by the evaporator probe,

which causes the end of defrost

Pr1

-58~1

65

65

38

IdF

Interval between

defrost cycles

(0÷10h) Determines the time

interval between the beginning of

two defrost cycles

Pr1

0 ~ 10 hours

6

6

6

MdF

(Maximum) length

for defrost

(0÷55min) When PP = n, (not

evaporator probe: timed defrost) it

sets the defrost duration, when PP =

y (defrost end based on temperature)

it sets the maximum length for defrost

Pr

0 ~ 55

minutes

40

40

60

Fdt

Drip time

(0÷10 min) time interval between

reaching defrost termination

temperature and the restoring of the

control’s normal operation. This time

allows the evaporator to eliminate

water drops that might have formed

due to defrost

Pr1

0 ~ 55

minutes





0