Installation and operations manual, Alarm signals, Other messages – Heatcraft Refrigeration Products PRO3 User Manual

Page 12: Technical data

Advertising
background image

1

Installation and Operations Manual

Alarm Signals

MESSAgE

CAUSE

OUTPUTS

P1

Room probe failure

Compressor output according
to parameters “Con” and “COF”

P

Evaporator probe
failure

Defrost end is timed

P3

Third probe failure Outputs unchanged

P4

Fourth probe
failure

Outputs unchanged

HA

Maximum
temperature alarm

Outputs unchanged

LA

Minimum
temperature alarm

Outputs unchanged

HA

Condenser high
temperature

It depends on the Ac
parameter

LA

Condenser low
temperature

It depends on the bLL
parameter

dA

Door open

Compressor and fans restarts

EA

External alarm

Output unchanged

Alarm Recovery

Probe alarms P1, P, P3 and P4 start some seconds after the fault
in the related probe; they automatically stop some seconds after
the probe restarts normal operation. Check connections before
replacing the probe.
Temperature alarms HA, LA, HA and LA automatically stop as soon
as the temperature returns to normal values.

Other Messages

MESSAgE MEANINg

Pon

Keyboard unlocked

PoF

Keyboard locked

noP

In programming mode: none parameter is present in Pr1
On the display the selected probe is not enabled

noA

None alarm is recorded

Technical Data

CHARACTERISTIC

DESCRIPTION

Housing

self extinguishing ABS

Case

XR40CX/XR60CX frontal 3x74 mm;
depth 60mm

Mounting

XR40CX/XR60CX panel mounting in a
71x9mm panel cut-out

Protection

IP0

Frontal protection

XR40CX/XR60CX IP65

Connections

Screw terminal block ≤ ,5 mm



wiring

Power supply

according to the model: 1Vac/dc,
±10%; 4Vac/dc, ±10%; 30Vac ±10%,
50/60Hz, 110Vac ±10%, 50/60Hz

Power absorption

3VA max

Display

3 digits, red LED, 14, mm high;

Inputs

Up to 4 NTC or PTC probes

Digital input

free voltage contact

Relay outputs

compressor: SPST 8(3) A, 50Vac; SPST
16(6)A 50Vac or 0(8)A 50Vac
defrost: SPDT 8(3) A, 50Vac
fan (XR60CX only): SPST 8(3) A, 50Vac
or SPST 5() A

Data storing

on the non-volatile memory (EEPROM)

Kind of action

1B

Pollution grade



Software class

A

Rated impulsive voltage 500V
Overvoltage Category

II

Operating temperature

0÷60 °C

Storage temperature

-30÷85 °C

Relative humidity

0÷85% (no condensing)

Measuring and
regulation range

NTC probe: -40÷110°C (-40÷30°F)
PTC probe: -50÷150°C (-58÷30°F)

Resolution

0,1 °C or 1°C or 1 °F (selectable)

Accuracy (ambient
temp. 5°C)

±0,7 °C ±1 digit