PRO

3

Side Mount Packaged Refrigeration System Installation and Operations Manual, May 008

9

PRO

3

Side Mount Packaged Refrigeration System

Max. & Min. Temperature Memorization

HOW TO SEE THE MIN. TEMPERATURE
1. Press and release the DOWN key.
. The “Lo” message will be displayed followed by the minimum

temperature recorded.

3. By pressing the DOWN key again or by waiting 5 seconds the

normal display will be restored.

HOW TO SEE THE MAX. TEMPERATURE
1. Press and release the UP key.
. The “Hi” message will be displayed followed by the maximum

temperature recorded.

3. By pressing the UP key again or by waiting 5 seconds the

normal display will be restored.

HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED
1. Hold press the SET key for more than 3 seconds, while the

max. or min temperature is displayed. (rSt message will
be displayed)

. To confirm the operation the “rSt” message starts blinking and

the normal temperature will be displayed

Main Functions

HOW TO SEE THE SET-POINT

1. Push and immediately release SET key: the
display will show the set point value

. Push and immediately release the SET key or wait 5 seconds to

display the probe value again

HOW TO CHANgE THE SET-POINT
1. Push SET for more than  seconds to change the set-point value
. The value of the set-point will be displayed and the °C or °F

LED starts blinking

3. To change the set value push UP or DOWN arrows within 10

seconds

4. To memorize the new set point value push SET key again or

wait 10 seconds

HOW TO START A MANUAL DEFROST

Push DEF key for more than  seconds and a manual

defrost will start.

HOW TO CHANgE A PARAMETER vALUE
To change a parameter value:

Enter the Programming mode by pressing the SET + DOWN

keys for 3 seconds (the °C or °F LED starts blinking)
Select the required parameter. Press SET to display its value.
Use UP or DOWN to change its value
Press SET to store the new value and move to the following

parameter

To exit: Press SET + UP or wait 15 seconds without pressing a key
NOTE: The set value is stored even when the procedure is exited by

waiting the time-out to expire.

1.

.
3.
4.

The Hidden Menu

The hidden menu Includes all the parameters of the instrument.
HOW TO ENTER THE HIDDEN PARAMETERS
1. Enter the Programming mode by pressing the Set + DOWN

keys for 3 seconds (the °C or °F LED starts blinking).

. Release the keys, then push again the Set+DOWN keys

for more than 7 seconds. The Pr label will be displayed
immediately followed from the HY parameter.
NOW YOU ARE IN THE HIDDEN MENU

3. Select the required parameter.
4. Press the SET key to display its value
5. Use UP or DOWN to change its value.
6. Press SET to store the new value and move to the following

parameter.

To exit: Press SET + UP or wait 15 seconds without pressing a key.
NOTE 1: If no parameter is present in Pr1, after 3 seconds the “noP”

message is displayed. Keep the keys pushed until the Pr2 message

is displayed.
NOTE 2: The set value is stored even when the procedure is exited

by waiting the time-out to expire.
HOW TO MOvE A PARAMETER FROM THE HIDDEN MENU TO

THE FIRST LEvEL AND vICE vERSA
Each parameter present in the HIDDEN MENU can be removed or
put into “THE FIRST LEVEL” (user level) by pressing SET + Down.
In HIDDEN MENU when a parameter is present in First Level the
decimal point is on.
HOW TO LOCK THE KEYBOARD
1. Keep the UP + DOWN keys pressed for more than 3 seconds.
. The “POF” message will be displayed and the keyboard will be

locked. At this point it will be possible only to see the set point
or the MAX o Min temperature stored

3. If a key is pressed more than 3 seconds the “POF” message will

be displayed.

To unlock the keyboard

Keep the UP + DOWN keys pressed for more than 3 seconds, until
the “Pon” message is displayed.

The continuous cycle

When defrost is not in progress, it can be activated by holding the
UP key pressed for about 3 seconds. The compressor operates to
maintain the ccS set point for the time set through the CCt parameter.
The cycle can be terminated before the end of the set time using the
same activation key UP for 3 seconds.
The on/off function
With “onF = oFF”, pushing the ON/OFF key, the instrument is
switched off. The “OFF” message is displayed. In this configuration,
To switch the instrument on, push again the ON/OFF key.

WARNING: Loads connected to the normally closed contacts of

the relays are always supplied and under voltage, even if the

instrument is in stand by mode.