Installation procedures, Installation method #1, Installation and operations manual – Heatcraft Refrigeration Products PRO3 User Manual

Page 4

Advertising
background image

4

Installation and Operations Manual

FIGURE 4: Cutout Location

2.62" TYP

20.25" TYP

22.75" TYP

CUTOUTS

2.62" TYP

20.25" TYP

28.75" TYP

CUTOUTS

FIGURE 6: Cutout Dimensions | Large Cabinet

FIGURE 5: Cutout Dimensions | Small Cabinet

CAUTION: Do not support any portion of the unit by the

drain pan.

Installation Procedures

NOTE:

Installation and maintenance to be performed only

by qualified personnel who are familiar with local codes and

regulations and are experienced with this type of equipment.

CAUTION: Make sure all power sources are disconnected

before any service work is done on units.

A.) Inspect packaging/unit for shipping damage

B.) Review the space and location requirements provided for your

method of installation.

C.)

Follow installation instructions listed in method #1 or #

Installation Method #1

Top Installation (See FIGURES 4, 5 and 6)

This installation method is the recommended installation method
in applications where it is feasible.

In order to install a unit using this method, you will need to provide
cutout slots for the “arms.” The unit should be placed on the wall
prior to setting and securing the roof of the box.

Please use the following guidelines when completing the installation
in this manner.
1. You will need to provide finished slots with the appropriate

dimensions in the box wall.

See FIGURES 5 and 6.

2. The slots can straddle a seam but they should not be on a seam.

See FIGURE 4.

3. The cut-out sections should not be placed in a location where

they would interfere with any cam locks.

4. It is preferred that a cam lock be placed in between the cutouts

to give additional support

5. The unit will need to be lifted to the appropriate height and

inserted into the open slots. The bottom of the unit should

be temporarily supported during the remainder of the installation

process (no portion of the unit should be supported by the

bottom of the evaporator section as this WILL cause damage to

the drain pan).

6. Set and secure the roof of the box and firmly attach the unit to

the box and carefully seal all seams and penetration points.