Label

Characteristic

Description

Menu/User

Level

Possible

Settings

DEFAULT SETTINGS

Low

Temp.

Medium

Temp.

High

Temp.

FANS (XR60CX ONLY)

Fnd

Fans delay after

defrost

(0÷55min) Interval between end of

defrost and evaporator fans start

Pr1

0 ~ 55

minutes





Not

Applicable

Fct

Temperature

differential

avoiding short

cycles of fans

(0÷59°C; Fct=0 function disabled).

If the difference of temperature

between the evaporator and the

room probes is more than the value

of the Fct parameter, the fans are

switched on

Pr

0~90

10

10

Not

Applicable

FSt

Fans stop

temperature

(-50÷50°C/1°F) setting of

temperature, detected by

evaporator probe, above which fans

are always OFF

Pr1

-58~1

35

35

Not

Applicable

ALARMS

ALC Temperature alarms

configuration

(Ab; rE) Ab= absolute temperature:

alarm temperature is given by the

ALL or ALU values. rE = temperature

alarms are referred to the set point.

Temperature alarm is enabled

when the temperature exceeds the

“SET+ALU” or “SET-ALL” values

Pr

rE = relative to

set point

Ab = absolute

Ab

Ab

Ab

ALU

MAXIMUM

temperature alarm

(SET÷110°C; SET÷30°F) when this

temperature is reached the alarm is

enabled, after the “ALd” delay time

Pr

ALL~ 30

38

50

50

ALL

Minimum

temperature alarm

-50.0 ÷ SET°C; -58÷30°F when this

temperature is reached the alarm is

enabled, after the “ALd” delay time

Pr

-58~ ALu

-5

15

30

How to Use the Hot Key

HOW TO PROgRAM A HOT KEY FROM THE INSTRUMENT

(UPLOAD)
1. Program one controller with the front keypad.
. When the controller is ON, insert the “Hot key” and push UP;

the “uPL” message appears followed a by flashing “End”

1. Push “SET” key and the End will stop flashing.
. Turn OFF the instrument remove the “Hot Key”, then turn it

ON again.

NOTE: The “Err” message is displayed for failed programming. In

this case push again o key if you want to restart the upload again

or remove the “Hot key” to abort the operation.
HOW TO PROgRAM A HOT KEY FROM THE INSTRUMENT

(DOWNLOAD)
1. Turn OFF the instrument.
. Insert a programmed “Hot Key” into the 5 PIN receptacle and

then turn the Controller ON.

3. Automatically the parameter list of the “Hot Key” is

downloaded into the Controller memory, the “doL” message is
blinking followed a by flashing “End”.

4. After 10 seconds the instrument will restart working with the

new parameters.

5. Remove the “Hot Key”.
NOTE: The message “Err” is displayed for failed programming. In

this case turn the unit off and then on if you want to restart the

download again or remove the “Hot key” to abort the operation.