Hearth & Home Technologies • BV4236DBI, BV4842DBI • 2209-900 Rev. N • 9/12

A. Pipe Clearances to Combustibles

Vent clearances are per vent manufacturer’s specifica-

tions. MUST be Listed B-Vent pipe.
WARNING! Risk of Fire! Maintain air space clearance to

vent.

DO NOT pack insulation or other combustibles:

• Between ceiling firestops

• Between wall shield firestops

• Around vent system

Failure to keep insulation or other material away from

vent pipe may cause over heating and fire.

8

Vent Clearances and Framing

B. Wall and Ceiling Penetration Framing

For a wall or ceiling penetration consult B-vent pipe manu-

facturer’s instructions to provide adequate clearances. Use

same size framing materials as those used in the wall or

ceiling construction. Firestop spacers must be used in wall

and ceiling penetrations per the B-Vent pipe manufacturer’s

specifications and national, regional and local codes.
Note: MUST terminate vertically.

C. Vertical Penetration Framing

WARNING! Fire Risk. DO NOT allow loose materials or

insulation to touch vent. Hearth & Home Technologies

Inc. requires the use of an attic shield.
The National Fuel Gas Code ANSI Z223.1 and NFPA 54

requires an attic shield constructed of 26 gauge minimum

metal that extends at least 2 in. (51 mm) above insulation.
Attic shields must meet specified clearance and be se-

cured in place.
Use B-vent manufacturer’s firestops to provide adequate

clearances.