TB7220 COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT

63-2635—03

14

0260

CPH for third Stage

Heat

9

1-12

Only shown if 3H/2C heat pump is selected.

0270

CPH for Auxiliary

Heat

9

1-12

Only shown if multi-stage heat pump is selected (heat

pump with more heat than cool stages).

0280

Continuous

Backlight

0

0—No

1—Yes

Always shown. If AC power not present the option is

overridden and normal backlight operation occurs.

0300

Changeover

1

0—Manual

1—Auto

Only shown if system has both heat and cool stages.

0310

Deadband

3°F

(2°C)

2 (1.5)—2°F (1.5°C)

3 (2.0)—3°F (2.0°C)

4 (2.5)—4°F (2.5°C)

5 (3.0)—5°F (3.0°C)

6 (3.5)—6°F (3.5°C)

7 (4.0)—7°F (4.0°C)

8 (4.5)—8°F (4.5°C)

9 (5.0)—9°F (5.0°C)

Only shown if Automatic Changeover Selected

0320

a

Temperature

Indication Scale

0

0—°F

1—°C

0330

a

Daylight Saving

1

0—Disabled

1—Enabled (US)

0340

Remote

Temperature Sensor

0

0—None

1—Outdoor for Display

2—Outdoor for Control

3—Remote 10K Indoor

4—Remote 20K Indoor

Averaging would not include on-board sensor. It is

accomplished by series/parallel combinations.

2 applies only to Heat Pump applications (allowing

compressor lockout while displaying temperature).

0350

Heat Pump

Compressor Lockout

0

0—None

15(-9.5)—15°F(-9.5°C)

20(-6.5)—20°F(-6.5°C)

25(-4.0)—25°F(-4.0°C)

30(-1.0)—30°F(-1.0°C)

35(1.5)—35°F(1.5°C)

40(4.5)—40°F(4.5°C)

45(7.0)—45°F(7.0°C)

Only shown for heat pump systems with more heat stages

than cool selected and remote sensor selection is outdoor

for control.

Must enforce a dead band between this and Auxiliary

Lockout

0360

Heat Pump Auxiliary

Lockout

0

0—None

40(4.5)—40°F(4.5°C)

45(7.0)—45°F(7.0°C)

50(10.0)—50°F(10.0°C)

55(13.0)—55°F(13.0°C)

60(15.5)—60°F(15.5°C)

Only shown for heat pump systems with more heat stages

than cool selected and remote sensor selection is outdoor

for control.

Must enforce a dead band between this and Heat Pump

Compressor Lockout.

0535

Temporary Occupied

Duration Limit

3

0—no duration

1—one hour

2—two hours

3—three hours

4—four hours

0 means no limit

0540

a

Number of Periods

4

2—2 Periods

4—4 Periods

Does not appear if Non-programmable is chosen.

Applies to all days of the week. With 2 selected the “Cancel

Period” option does not appear on the display.

0580

Minimum

Compressor Off

Time

5

0—Off

2—2 minutes

3—3 minutes

4—4 minutes

5—5 minutes

Only shown if system has cool stages.

0600

Heat Temperature

Range Stops

90

40 to 90°F (4 to 32°C)

Only shown if system has heat stages.

0610

Cool Temperature

Range Stops

50

50 to 99°F (10 to 37°C)

Only shown if system has cool stages.

Table 6. Installer Setup Menu. (Continued)

Installer

Setup

Number

Installer Setup

Name

Default

Setting

All Settings

Notes

a

Setting available for modification in both the Installer and User setup modes.