Minimum-off timer compressor protection, Economizer/tod logic (table 8), Heat pump temperature lockouts – Honeywell COMMERCIALPRO TB7220 User Manual

Page 19: Economizer/to d logic (table 8), Partially locked screen, Temperature recovery, Dual fuel heat pump and outdoor temperature sensor

Advertising
background image

TB7220 COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT

19

63-2635—03

Partially Locked Screen

When partially locked:

— Pressing a locked key prompts the screen to indicate

SCREEN LOCKED for five to seven seconds.

— Pressing an unlocked key with SCREEN LOCKED active

removes SCREEN LOCKED from the display.

PARTIAL LOCKOUT 1
This mode locks all keys except HOLIDAY, OVERRIDE, and

temperature Up/Down arrows:

— User can change the temperature setpoint, but cannot

change schedule settings.

— The temporary temperature change lasts until next

scheduled period. The screen displays that time.

— User can change the temperature setpoint, but cannot

change schedule settings.

— Pressing HOLIDAY sets the temperature to the Unoccupied

setting for the selected period of time. The next Occupied

period switches back to the program settings.

— Pressing OVERRIDE sets the temperature to the Occupied

setting for the selected period of time. The next Unoccupied

period switches back to the program settings.

— To cancel the temperature override and follow the

programmed schedule, press CANCEL.

— To unlock the screen, see Advanced Settings section.

PARTIAL LOCKOUT 2
This mode locks all keys except HOLIDAY and OVERRIDE:

— Pressing HOLIDAY sets the temperature to the Unoccupied

setting for the selected period of time. The next Occupied

period switches back to the program settings.

— Pressing OVERRIDE sets the temperature to the Occupied

setting for the selected period of time. The next Unoccupied

period switches back to the program settings.

— To cancel the temperature override and follow the

programmed schedule, press CANCEL.

— To unlock the screen, see Advanced Settings section.

Temperature Recovery

The thermostat is equipped with a feature to eliminate

guesswork when setting a schedule. That is, the user need not

know the amount of time for the HVAC system to bring the

space to temperature (without overshoot) prior to the

scheduled time.The thermostat manages that automatically.

Simply set the program schedule to the desired time to have

the space at comfort temperature. In addition, program the

temperature to this comfort temperature. The thermostat

activates the heating or cooling at the proper time to reach the

scheduled temperature at the scheduled time.

NOTE: The setpoint changes gradually to use economical

stages and avoid overshoot.

For example—the space will be occupied at 8:00 AM and the

desired temperature is 70°F. Set the OCC 1 period for 8:00 AM

and 70°F. The thermostat turns on the heat prior to 8:00 AM to

raise the temperature to 70°F by 8:00 AM.

The thermostat provides an alert that the heating or cooling

system is coming on before a scheduled time by displaying

“Recovery” on the screen.

Minimum-Off Timer Compressor Protection

The thermostat has an adjustable Minimum-Off Timer that can

be set from zero to five minutes (Factory Setting—five

minutes). The Minimum-Off Timer can be bypassed through

the Installer System Test or it can be bypassed permanently by

setting the Minimum-Off Timer to 0 minutes in the Installer

Setup. The Minimum-Off Timer is activated after the

compressor turns off:

— If the thermostat is system powered (common wire), the

Minimum-Off Timer is also activated upon initial startup and

after power interruptions.

— If there is a call for cooling or heating during the Minimum-

Off Time, the thermostat displays “Wait.”

— When the Minimum Off Timer expires, “Cool On” or “Heat

On” (heat pumps only)” appears solidly in the display and

the compressor and fan turn on.

Economizer/TOD Logic (Table 8)

Table 8. Operation of Terminal A.

Heat Pump Temperature Lockouts

Dual Fuel Heat Pump and Outdoor Temperature
Sensor

In this operation, there is no external fossil fuel kit (dual fuel kit)

installed; the thermostat controls this function:

1. Choose correct heat pump application in ISU 0170.

2. Choose Outdoor Temperature Sensor for Heat Pump

Temperature Lockouts Option in ISU 0340.

3. Choose appropriate Balance Point Temperature in

ISU 0350.

OPERATION IN HEAT MODE ABOVE BALANCE POINT (OUTDOOR
TEMPERATURE)
When the outdoor temperature is above the selected Balance

Point Temperature (ISU 0350), only the compressor operates

and the fan (G terminal) energizes when the thermostat calls

for heat.

OPERATION IN HEAT MODE BELOW BALANCE POINT (OUTDOOR
TEMPERATURE)
When the outdoor temperature is below the selected Balance

Point Temperature (ISU 0350), only the Fossil Fuel (auxiliary

heat) operates and the fan (G terminal) does not energize

when the thermostat calls for heat.

Heat Pump with Auxiliary (Backup) Heat and Outdoor
Temperature Sensor

1. Choose correct heat pump application in ISU 0170.

2. Choose Outdoor Temperature Sensor for Control

Option in ISU 0340.

3. Choose Compressor Lockout Temperature in

ISU 0350.

4. Choose Auxiliary Lockout Temperature in ISU 0360.

Effective

Occupancy

Call for

Cool

Terminal A

Economizer

TOD

Occupied

Energized

Energized

Unoccupied Yes

Energized

De-energized

No

De-energized

De-energized

Override

Energized

Energized

Advertising