Terminal “a” wiring details for economizers – Honeywell COMMERCIALPRO TB7220 User Manual

Page 6

Advertising
background image

TB7220 COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT

63-2635—03

6

Fig. 11. Restrict wires to shaded area of wire hole.

Table 4. Wiring Diagrams.

Table 5. Terminal Designation Descriptions.

NOTES:

1.

When used in a single-transformer system, leave

metal jumper wire in place between Rc and R. If

used on a two-transformer system, remove metal

jumper wire between Rc and R.

2.

Common wire is optional when thermostat is used

with batteries. When using separate transformers

for heating and cooling, the common must come

from the cooling transformer.

3.

If thermostat is configured for a heat pump in the

Installer Setup, configure changeover valve for

cool (O-factory setting) or heat (B).

4.

Reference economizer literature for wiring details.

When set for economizer operation, the A terminal

provides the occupancy signal. (Power indicates

occupied.)

5.

Sensor wires must have a cable separate from the

thermostat control cable.

Terminal “A” Wiring Details for Economizers

— Wire the A terminal to the W7212 “N” terminal, or the

W7459 “TR” terminal.

— When using dual transformers at the thermostat, the cooling

transformer must power the economizer.

— The A signal is powered from the R terminal and energizes

the economizer to signal occupied status and drive the

damper to the set minimum position.

System Type

Wallplate Terminal

Identifications

Wiring Diagram

Figure

Standard Heat/Cool Conventional

12, 13

Heat Only

Conventional

14

Cool only

Conventional

15

Standard Multistage

up to 2 Heat/2 Cool

Conventional

16, 17

Heat Pump

(No Auxiliary Heat)

Heat Pump

18, 19

Heat Pump

(with Auxiliary Heat)

Heat Pump

20, 21

Multiple T7770A

Sensors

26, 27, 28

Multiple C7189U

Sensors

29

WALLPLATE

M22266

WALL OPENING

WIRE

SHADED AREA

Terminal

Designation

Description

Rc

(see Note 1)

Power for cooling—connect to secondary side

of cooling system transformer.

R

(see Note 1)

Power for heating—connect to secondary side

of heating system transformer.

Y

Compressor output.

C

(see Note 2)

Common wire from secondary side of cooling

system transformer.

W

Heat relay.

G

Fan relay.

W2

Second stage heat relay.

Y2

Second stage cooling.

O/B

(see Note 3)

Changeover valve for heat pumps.

A

(see Note 4)

Economizer/Time-Of-Day (TOD) output—

powered via R terminal.

S1

(See Note 5)

Optional outdoor or indoor remote sensor.

S2

(See Note 5)

Optional outdoor or indoor remote sensor.