TB7220 COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT

23

63-2635—03

Heating equipment is running in

the cool mode.

Heating equipment is not a heat pump but

System Type (ISU 0170) is set to Heat

Pump.

Set System Type (ISU 0170) to match the

installed heating and/or cooling equipment.

Heating equipment does not turn

off and heat temperature setting

is set below room temperature

(Heat On is not in the display).

Heating equipment is not a heat pump but

System Type (ISU 0170) is set to Heat

Pump.

Set System Type (ISU 0170) to match the

installed heating and/or cooling equipment.

Cannot set the system setting to

Heat.

System Type (ISU 0170) is set to Cool

Only.

Set System Type (ISU 0170) to match the

installed heating and/or cooling equipment.

Cannot set the system setting to

Cool.

System Type (ISU 0170) is set to Heat

Only or Heat Only with Fan.

Set System Type (ISU 0170) to match the

installed heating and/or cooling equipment.

Heat On is not in the display.

System setting is not set to Heat and/or

temperature setting is not set above room

temperature.

Set the system setting to Heat and set the

temperature setting above the room temperature.

Cool On is not in the display.

System setting is not set to Cool and/or the

temperature setting is not set below room

temperature.

Set the system setting to Cool and set the

temperature setting below the room temperature.

Wait is in the display.

Compressor minimum off timer is active.

Wait up to five minutes for the cooling or heating

(heat pump) equipment to turn on.

“Screen Locked” appears on the

screen and all or some of the

keys do not respond.

The keypad is fully or partially locked.

Check ISU 0670 to change keypad locked

options.