TB7220 COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT

5

63-2635—03

Install Wallplate (See Fig. 8)

Mount the thermostat horizontally on the wall:

1. Pull the wires through the wire hole on the wallplate.

2. Position the wallplate on the wall with the arrow pointing

up. Level the wallplate for appearance only.

3. Use a pencil to mark the mounting holes.

4. Remove the wallplate from the wall and drill two 3/16 in.

holes in the wall (if drywall) as marked. For firmer

material such as plaster, drill two 7/32 in. holes. Tap the

wall anchors (provided) into the drilled holes until flush

with the wall.

5. Pull the wires through the wire hole on the wallplate and

position the wallplate over the wall anchors.

6. Insert the mounting screws into the wall anchors and

tighten.

Fig. 8. Install wallplate.

WIRING

CAUTION

Electrical Shock Hazard.

Can cause electrical shock or equipment damage.

Disconnect power supply before connecting wiring.

IMPORTANT

— All wiring must agree with applicable codes,

ordinances and regulations.

— Use 18 gauge thermostat wire. Shielded cable is not

required.

NOTES:

Refer to Table 5 for terminal designation

descriptions.

See Fig. 12 through 21 for wiring diagrams for

specific equipment applications.

1. Select set of terminal identifications that correspond to

your system type (conventional or heat pump). See Fig. 9.

Fig. 9. Terminal identifications for system type.

2. Loosen screw terminals used for the application.

3. Insert the wires into the terminal block and tighten each

screw terminal. See Fig. 10.

Fig. 10. Insert wires into terminal block.

4. Push excess wire back into the wall opening and restrict

wires to the shaded area. See Fig. 11.

5. Plug the wall opening with nonflammable insulation to

prevent drafts from affecting the thermostat.

WALL

MOUNTING

HOLES

M13665

MOUNTING

SCREWS (2)

WALL

ANCHORS (2)

WIRES THROUGH WALL

AND WIRE SLOT

M13663

C
G
Y
W
RC
R

W2

Y2

A

S1
S2

SCREW

TERMINALS

HEAT PUMP

CONVENTIONAL

1

FACTORY INSTALLED JUMPER.

1

C
G
Y
O/B
RC
R

W1

Y2

S1
S2

M13666

WIRE HOLE

Advertising