SC Series Instruction Manual page 101

Hig

h-L

ev

el

In

pu

t C

han

nel

12

12.2.4 “3-wire Voltage”

Amplifiers with Single-wire

Shunt Cal

Use the following wiring diagram when connecting an amplified transducer with a
3-wire voltage amplifier with single-wire shunt calibration to a High-Level Input
channel. An example of a such device includes

transducers with Option 2d or Option 2g internal amplifiers (with shunt cal)

The High-Level Input channel’s Configuration Jumpers must be set as follows for
proper operation. See “Excitation and Signal Jumpers” on page 106.

(+)Excitation supply: “+28 VDC”

(-)Excitation supply: “GND”

Signal type: “voltage”

Signal reference: “differential”

Figure 12-3: “3-wire Voltage Amp w/Single-Wire Shunt Cal” Connection to High-Level Input

Channel