5 channel menu, 1 dac setup sub-menu, Dac. channel menu item – Honeywell SC1000 User Manual

Page 133: Dac. source menu item, Dac. zero-scale menu item, Dac. full-scale menu item

Advertising
background image

SC Series Instruction Manual page 133

DA

C Ou

tpu

t Cha
nnel

14

14.5 Channel Menu

Each DAC Output channel is configured and calibrated via its channel menu.
Detailed instructions on operating the instrument in the SETUP Menu mode can
be found in “SETUP Menu mode” on page 23. A diagram of all menus is located
in “Setup Menu Reference” on page 157.

14.5.1

DAC SETUP

Sub-Menu

This sub-menu contains four items that controls the analog output of the channel.

DAC. CHANNEL

Menu Item

This chooses which channel will drive the Digital-to-Analog Converter (DAC) out-
put.

DAC. SOURCE

Menu Item

This designates the data source of the channel monitored by the analog output.
Each channel has three data sources: the live tracking value (TRACK), its highest
value (PEAK), and its lowest value (VALLEY).

The options for this menu item are:

TRACK

” means the live tracking value of the channel.

PEAK

” means the highest value of the channel since the peak/valley detector

was last cleared.

VALLEY

” means the lowest value of the channel since the peak/valley detector

was last cleared.

DAC. ZERO-SCALE

Menu Item

This specifies what value, in engineering units, corresponds to zero output on the
Analog Output.

“Zero output” might be 0 Volts, 2.5 Volts, 5 Volts, 4 mA or 12 mA depending on if
the channel has a voltage or current output and how it is configured. See the
“Digital-to-Analog Output” section of this chapter for details.

This menu item is not automatically updated by another channel’s Signature Mod-
ule
equipped transducer.

DAC. FULL-SCALE

Menu Item

This specifies what value, in engineering units, corresponds to full output on the
Analog Output.

“Full output” might be 5 Volts, 10 Volts or 20 mA depending on if the channel has
a voltage or current output and how it is configured. See the “Digital-to-Analog
Output” section of this chapter for details.

This menu item is not automatically updated by another channel’s Signature Mod-
ule
equipped transducer.

Advertising
This manual is related to the following products: