2 error message list, Error 05, divide by zero, Error 07, square root – Honeywell SC1000 User Manual

Page 152: Error 09, log/ln, Error 16, +15v supply high, Error 17, +15v supply low, Error 18, -15v supply high, Error 19, -15v supply low, Error 20, channel >maxch, Error 21, blown stack

Advertising
background image

page 152 008-0608-00

17.2 Error Message List

Error 05,

DIVIDE BY ZERO

A Mathematics Virtual channel has attempted to divide by zero.

Error 07,

SQUARE ROOT

A Mathematics Virtual channel has attempted to take the square root of a negative
number.

Error 09,

LOG/LN

A Mathematics Virtual channel has attempted to take the logarithm of either zero or a
negative number.

Error 16,

+15V SUPPLY HIGH

The internal +15 VDC power supply is generating a voltage that is too high.

Error 17,

+15V SUPPLY LOW

The internal +15 VDC power supply is generating a voltage that is too low. Check the
wiring between the instrument and the transducer or amplifier.

Error 18,

-15V SUPPLY HIGH

The internal -15 VDC power supply is generating a voltage that is too high (more pos-
itive). Check the wiring between the instrument and the transducer or amplifier.

Error 19,

-15V SUPPLY LOW

The internal -15 VDC power supply is generating a voltage that is too low (more nega-
tive).

Error 20,

CHANNEL >MAXCH

An invalid channel number has been encountered by the instrument. Restart the
instrument. If this error persists, contact our Service department with the information
found in the

SYSTEM MENU

->

SOFTWARE REV.

menu item.

Error 21,

BLOWN STACK

The instrument’s software stack has overflowed. Restart the instrument. If this error
persists, contact our Service department with the information found in the

SYSTEM MENU

-

>

SOFTWARE REV.

menu item.

Error 22,

TYPE NOT FOUND

The instrument has not been programmed to understand the type of channel. Contact
our Service department with the information found in the

SYSTEM MENU

->

SOFTWARE REV.

menu item.

Error 23,

CAN'T RENDER FS

The full-scale value of the transducer cannot be rendered on the display with the
selected

DISPLAY SETUP

menu settings. Change the

DISPLAY SETUP

menu settings to better

match the transducer’s capacity.

Error 24,

SIG.MOD CRC ROM

A checksum error occurred while reading a Signature Module’s read-only-memory.
Check the wiring and restart the instrument. This error may occur with very long cable
lengths.

Error 25,

SIG.MOD CRC READ

A checksum failure occurred reading data from a Signature Module. Check the wiring.
This error may be caused by a faulty Signature Module.

Error 26,

NO SIG.MOD.

No Signature Module was detected during

UPDATE SIG.MOD.

or

DEFAULT SIG.MOD.

Check

wiring.

Error 27,

S.EE WRITE NAK

The channel’s EEPROM could not be detected during a write operation. Check that
the channel’s address jumpers are set properly so that each card has an unique
address.

Error 28,

S.EE READ NAK

The channel’s EEPROM could not be detected during a read operation. Check that
the channel’s address jumpers are set properly.