Limi

ts

9

Figure 9-4: Limit Operation when

LIMIT.ENERGIZE

=

SIGNAL OUTSIDE

9.3.6

LIMIT.LATCHING

Menu Item

This specifies whether to latch the activated limit so that only manually clearing the
limit will deactivate it. A latched limit can be manually cleared by pressing the
[CLEAR] button, sending the “F8” serial communications command, or by using the
Function Input #2 (Clear Peak/Valley & Limits pin on the System Connector. See
“Function Input Pins” on page 37.

The options for this menu item are:

ON

” means that once a signal activates the limit, the limit will remain activated until

it is reset.

OFF

” means that the limit will deactivate immediately when the signal crosses the

return point.

9.3.7

LIMIT.CHANNEL

Menu Item

This specifies the channel that is monitored by this limit.

9.3.8

LIMIT.SOURCE

Menu Item

This designates the data source of the channel monitored by this limit. Each channel
has three data sources: the live tracking value (TRACK), its highest value (PEAK),
and its lowest value (VALLEY).

The options for this menu item are:

TRACK

” means the live tracking value of the channel.

PEAK

” means the highest value of the channel since the peak/valley detector was

last cleared.

VALLEY

” means the lowest value of the channel since the peak/valley detector was

last cleared.

9.3.9

LEAVE MENU

Menu

Item

When the menu item is displayed, press [ENTER] to leave this menu. Press [EXIT] to
return to the RUN mode.