Known point x/y menu items, Notice – Honeywell SC1000 User Manual

Page 70

Advertising
background image

page 70 008-0608-00

Figure 10-2: Shunt Calibration Resistor Location

To verify proper transducer operation, you can apply the shunt resistor to the trans-
ducer while the instrument is in the RUN mode. Press and hold the [ENTER] button
for three seconds; this will apply the shunt resistor and display the reading.

KNOWN POINT x/y

Menu Items

This enters the engineering units for the known-load calibration points. These points
must match the actual loads that you will apply to the instrument during calibration.
The number of calibrations points depends on the

CALIBRATION TYPE

.

When using the 2-Point Known Load Calibration type, the following menu items are
available:

KNOWN POINT 1/2

”: point 1 of 2, usually 0% of the transducer’s full-scale capacity.

KNOWN POINT 2/2”

: point 2 of 2, usually 100% of the transducer’s full-scale capacity.

When using the 3-Point Known Load Calibration type, the following menu items are
available:

KNOWN POINT 1/3

”: point 1 of 3, usually 0% of the transducer’s full-scale capacity.

KNOWN POINT 2/3

”: point 2 of 3, usually 50% of the transducer’s full-scale capacity.

KNOWN POINT 3/3

”: point 3 of 3, usually 100% of the transducer’s full-scale capacity.

When using the 5-Point Known Load Calibration type, the following menu items are
available:

KNOWN POINT 1/5

”: point 1 of 5, usually 0% of the transducer’s full-scale capacity.

KNOWN POINT 2/5

”: point 2 of 5, usually 25% of the transducer’s full-scale capacity.

KNOWN POINT 3/5

”: point 3 of 5, usually 50% of the transducer’s full-scale capacity.

KNOWN POINT 4/5

”: point 4 of 5, usually 75% of the transducer’s full-scale capacity.

KNOWN POINT 5/5

”: point 5 of 5, usually 100% of the transducer’s full-scale capacity.

These menu items are only available with the Known-Load Calibration types.

NOTICE

To insure both correct operation of the transducer and application of the load,
the instrument expects the voltage applied at each known-load point to be
increasing. For example, the load applied at Known-Load Point 2/2 must
cause the transducer to produce a more positive voltage than at Known-Load
Point 1/2.

Advertising
This manual is related to the following products: