Chapter 11 ac/ac-lvdt input channel, 1 features, Chapter 11, “ac/ac-lvdt input channel – Honeywell SC1000 User Manual

Page 79

Advertising
background image

SC Series Instruction Manual page 79

AC

/A

C-L

VDT I
nput Ch

annel

11

Chapter 11

AC/AC-LVDT Input Channel

11.1 Features

The AC/AC-LVDT Input channel provides an AC excitation voltage to and accepts
AC signals from LVDT (Linear Variable Differential Transformer) transducers.
These signals are digitized, converted into engineering units, and placed into the
track, peak and valley data values of the channel. Setup and calibration of the
channel are made manually through the SETUP mode.

The analog-to-digital converter features adjustable digital, low-pass filtering, 12- to
18-bit resolution (depending on the filter setting) and has several different input
ranges. These many input ranges allow ±25,000 count resolution (at the slowest
filter setting) for a wide variety of LVDT outputs.

The AC/AC-LVDT Input channel is calibrated to the transducer by using known-
displacement calibration.

Two rear panel control inputs can be field-configured for such functions as remote
tare, disabling peak/valley detection and clearing the peak/valley values. A stan-
dard voltage or optional current digital-to-analog output is also provided.

NOTICE

To use a DC/DC LVDT with an SC instrument, use a High-Level Input channel
instead of an AC/AC-LVDT Input channel.

Advertising
This manual is related to the following products: