Technician repair removal and replacement procedures 115

NOTE:

This procedure is specifically for the removal of the Type 1 flow meter.

1.

Power down the MCS unit ("

Powering down the MCS unit

" on page

24

).

2.

Shut off the water flowing into the MCS unit ("

Shutting off the water

" on page

25

).

3.

Remove the bottom fan unit ("

Removing the bottom fan unit

" on page

44

).

4.

Relocate the power inlet box ("

Relocating the power inlet box

" on page

93

).

5.

Remove the condensation pump and sensors ("

Removing the condensation pump and sensors

" on

page

47

).

6.

Remove the bottom heat exchanger unit ("

Removing the heat exchanger unit with couplers

" on page

59

).

7.

Remove the magnetic solenoid valve ("

Removing the magnetic solenoid valve

" on page

82

).

8.

Remove the AC transfer switch ("

Removing the AC transfer switch

" on page

26

).

9.

Using the 46-mm wrench (included in the miscellaneous hardware kit), loosen the two flow meter
union nuts securing the flow meter in place.

WARNING:

To reduce the risk of electric shock or damage to the equipment, use extreme

caution when removing and replacing components that involve water around the electrical

wires and unsecured power inlet box. There is great risk of electrical shock when water is used

near electricity.

WARNING:

To reduce the risk of electric shock or damage to the equipment, be prepared to

clean up the water from the disconnected water line with towels and sponges.