Thermal and air flow performance, Environmental specifications, Hp 10642 g2 rack specifications – HP 403349-003 User Manual

Page 143

Advertising
background image

Specifications 143

Thermal and air flow performance

Maximum thermal and air flow performance
parameters

Specifications

Air temperature—inlet to rack-mounted components

25ºC (68ºF)

Chilled water temperature

7º–10°C (45º–50°F)

Total rack-mounted component air flow

2,600 cfm or less at 0 or more pressure drop
across the rack-mounted components

Chilled water flow rate

21 gal/min

Chilled water pressure differential at flow needed to
meet thermal specifications

2.0 bar delta pressure

Heat lost to room

approximately 10% maximum depending on
the MCS settings and room temperature

Heat transferred to cooling fluid

35 kW maximum

Environmental specifications

Features Specifications

Operating temperature

5ºC to 35ºC (41ºF to 95ºF)

Non-operating temperature 0ºC to 60ºC (32ºF to 140ºF)
Transit temperature

-30ºC to 60ºC (-22ºF to 140ºF), up to 72 hours

Storage temperature

-20ºC to 60ºC (-4ºF to 140ºF)

Operating humidity

20 to 80% relative humidity (non-condensing)

Non-operating humidity

5 to 95% relative humidity (non-condensing)

Operating altitude

-76.2 to 3,048 m (-250 to 10,000 ft)

Non-operating altitude

-76.2 to 9,144 m (-250 to 30,000 ft)

HP 10642 G2 Rack specifications

U height Width

Depth

Dynamic load (gross) Static load

42U 600

mm

(23.82 in)

1,000 mm
(39.37 in)

907.18 kg (2,000 lb)

907.18 kg (2,000
lb)